![]() |
![]() |
![]() |
Engineering
> Fire & Life-Safety > Testing
Policies > Emergency Lights
Fire and Life-Safety Group (FLS)Emergency Lights Policies and ProceduresIntroductionThis document was prepared to list some but not all of the requirements based on the latest edition of adopted codes in 2004. Please ensure that all the requirements of applicable codes at the time of new installations or changes to existing installations are verified and implemented. The following text summarizes the code requirements for “Performance of System” and for “Testing Maintenance.” Performance of SystemSection 7.9.2.1 of the 2003 Life Safety Code (NFPA-101) states that emergency illumination is to be provided for not less than 1½ hour in the event of failure of the normal lighting system. Emergency lighting facilities are to be arranged to provide initial illumination of not less than an average of 10.8 lux (1 ft-candles) along the path of egress at the floor level. Emergency illumination levels are permitted to decline to not less than an average of 6.5 lux (0.6 ft-candle), and not less than 6.5 lux (0.6 ft-candle) at the end of the 1½ hours at any point. Additionally, a maximum-to-minimum illumination uniformity ratio of 40 to 1 is not to be exceeded. Section 7.9.2.2 of NFPA-101 states that the emergency lighting system is to be arranged to provide the required illumination automatically in the event of any interruption of normal lighting due to any of the following:
Section 7.9.2.3 of NFPA-101 states that if emergency generators are used for back-up, then the generators providing power to emergency lighting systems are to be installed, tested and maintained in accordance with NFPA-110, Standard for Emergency and Standby Power Systems . Section 7.9.2.4 of NFPA-101 states that when battery-operated emergency lights are utilized, they are to use only reliable types of rechargeable batteries provided with suitable facilities for maintaining them in proper charge condition. Batteries used in such lights or units are to be appr oved for their intended use and are to comply with NFPA-70, National Electrical Code . Section 7.9.2.5 of NFPA-101 states that the emergency lighting system is to be either continuously in operation or is to be capable of repeated automatic operation without manual intervention. Testing and MaintenanceSection 7.9.3.1 of NFPA-101 states that required emergency lighting systems are to be tested in accordance with one of the three options offered in the following sections. Section 7.9.3.1.1 of NFPA-101 states that testing of required emergency lighting systems is to be permitted as follows:
Section 7.9.3.1.2 of NFPA-101 states that testing of required emergency lighting systems utilizing self-testing/self-diagnostic battery operated equipments is to be permitted as follows:
Section 7.9.3.1.3 of NFPA-101 states that testing of required emergency lighting systems utilizing computer-based, self-testing/self-diagnostic battery operated equipment is to be permitted as follows:
|
||||
| Home
| Contact Us |